EU
CLASSIFICATION OF CONSTRUCTION PRODUCTS FOR RESISTANCE TO FIRE
- EXCLUDING VENTILATION SERVICES - AN OVERVIEW OF EN 13501-2.
Why the need for a new system?
In the past, the fire testing of construction systems for Resistance
to Fire has varied in different EU member states. This is because
each country has evolved its own methods, using furnaces of different
sizes, with different fuels, and different characteristics. While
the nominal fire exposure has been similar, these variations mean
that test results from different countries are difficult to compare.
Some countries have different requirements to others.
The new Euroclass system for Resistance to Fire, prEN 13501 -2,
reflects new fire test provisions for these differences, not by
changing the design of furnaces, but by rationalising the method
by which the temperatures in the furnace are measured, using new
'plate thermocouples', higher pressurisation of the furnaces and
other adjustments.
In general, this means that test results are comparable across
the EU, regardless of the national location of the fire test laboratory.
For the UK, it means that the test exposure is a little more severe
than before, and some products may be 'rated' or classified at
a slightly poorer level than previously. This is partly due to
new harmonised Resistance to Fire test methods and the new EU classification
of fire resistance data provided by these tests.
New Fire Classification Methods
When compared to existing UK nomenclature and that of some other
countries, the way the EU expresses the classification of the
test results is different. Despite the changes, requirements
already used in most EU member states will still be available
in the overall classification.
EU member states will be permitted to select the particular performance
appropriate to national requirements, and may well ignore some
parts of the classification. However, manufacturers will be required
to use the entire classification system when supplying construction
systems into other EU countries.
Fire Exposure Level
In most system applications, the fire exposure conditions will
be the same, but some applications require different fire exposures
to be evaluated. Fire tests will be made selecting from 5 fire
exposure scenarios:
5 FIRE EXPOSURE SCENARIOS
[1] The standard temperature-time curve (post flashover)
[2] The slow heating curve (smouldering fire)
[3] The 'semi-natural fire'
[4] The external fire exposure curve
[5] Constant temperature attack
................
[1] The standard temperature-time curve (post flashover fire)
This is defined by:
Temperature T = 345log10(8t +1) +20
Where t = time for exposure [minutes], T = 0C. This is the generalised
fire scenario that most construction systems will be subjected
to, representing a fully developed fire in a compartment.
[2] The slow heating curve (smouldering fire)
This exposure is only suitable when heat reactive elements may
be susceptible, or reduced by exposure, in the growth stage of
a fire below 500 0C. Further details are given in the test document
EN 1363-2
[3]
The 'semi-natural fire'
In this fire exposure, the fire gas temperatures adjacent to the
soffit of a ceiling shall reach 1000 0C within 10 to 20 minutes
of the start of the test, and is usually provided by fire from
a softwood timber crib. Further detail is available in test method
prENV 13381-1
[4] The external fire exposure curve.
This is a time-temperature relationship representing the exposure
of the external face of a wall to a fire emerging from a window
in the building, or from a free burning external fire. Further
detail is available in test method EN 1363-2
[5] Constant temperature attack.
Some elements will be evaluated by a notional constant value of
temperature. For example -
20 0C for evaluating the leakage rate of smoke control doors at
ambient temperature.
200 0C for evaluating the leakage rate of medium temperature smoke
control doors.
500 0C for evaluating the fire performance of raised floors.
1000 0C for evaluating soot fire resistance of chimneys and chimney
related products.
Resistance to Fire Characteristics
EC document Interpretive Document2 requires the assessment of the
characteristic
'Load-bearing capacity and/or Integrity in fire and/or Insulation
in fire'.
Other characteristics are also named, as indicated in the following
table. Many of these characteristics will only be used according
to particular member state requirements. However, manufacturers
who export goods to other EU Member States will be required to
have data available on all the 'characteristics'.
Summary of Resistance to Fire characteristics
:
|
DESIGNATORY LETTER
|
CHARACTERISTIC
|
PURPOSE
|
|
R
|
Load bearing capacity
|
To maintain load bearing without loss of structural ability
|
|
E
|
Integrity
|
To withstand fire exposure, on one side only, without
fire passage to the other side as flames or hot gases,
which may cause ignition on the unexposed side
|
|
I
|
Insulation
For doors or shutters, one of I1 or I2 will
be used depending on measuring conditions
|
To withstand fire exposure, on one side only, without
the transmission of fire as a result of significant transfer
of heat from the hot side to the cold side, so that ignition
of the cold surface, materials near it, or radiation onto
people close by are avoided.
|
|
W
|
Radiation
|
The ability of the element to withstand fire exposure
on one side only, and to reduce the transmission
of fire, from significant radiated heat through the element,
from the unexposed side to adjacent materials.
Satisfying I will normally satisfy W for the same period
of time.
|
|
M
|
Mechanical action
|
The ability of the element to withstand impact of a predefined
force, shortly after the time for the desired R, E or I
classification.
|
|
C
|
Self closing
|
The ability of a door or shutter assembly to close automatically,
thereby shutting an opening, irrespective of the availability
of a power supply [pass/fail]
|
|
S
|
Smoke leakage
Sa at ambient temp.
Sm at
ambient and at 2000C
|
The ability of the element to reduce or eliminate the
passage of gases or smoke from one side of the element
to the other
|
|
G
|
'Soot fire' resistance
|
The ability of the element to resist soot fires in chimneys
and chimney related products, including aspects of leakage
and thermal insulation
|
|
K
|
Fire protection ability
|
The ability of a wall or ceiling covering to provide for
the material behind the covering protection against ignition,
charring and other damage, for specific periods.
Coverings are the outermost parts of elements such as
walls, floors and roofs.
|
Classification Periods of Fire Resistance
The classification period is declared in minutes, using one
of the periods 15, 20, 30, 45, 60, 90, 120, 180, 240 or 360.
The requirement may vary between different EU member states.
Declaration of Performance
Combinations of 'designatory letters', as appropriate to the
application, are used as part of the classification of performance
for Resistance to Fire, supplemented by the time, 'tt' in minutes,
of the nearest lowest class satisfied. When characteristics are
combined, the time declared will be that for the characteristic
having the shortest time.
For example, an element with a load-bearing
capacity of 155 minutes, integrity of 80 minutes, and insulation
of 42 minutes will be classified as R 120 / RE 60 / REI 30.
For load-bearing elements, the classes
shall be expressed as -
REI
tt, - where 'tt' is the time satisfying the load bearing capacity,
integrity & insulation criteria.
RE tt - where 'tt' is the time satisfying the load-bearing
capacity & integrity criteria.
R tt - where 'tt' is the time satisfying the load-bearing
capacity criterion alone.
For non load-bearing elements, the classes
are -
EI tt - where 'tt' is the time satisfying the
integrity and insulation criteria
E tt - where 'tt' is the time satisfying the integrity criterion
alone.
Other Classification
Parameters :
ADDITIONAL CLASSIFICATION PARAMETER
W - when the radiation criteria is required
and has been satisfied, the designatory
Letter W is used in a similar way to R, E and I criteria,
e.g. REW 30 or EW 30.
EXPANDED PERFORMANCE PARAMETERS
Similarly, the classification may be expanded, according
to requirements, as
| M - |
used as REI 30-M |
| C - |
for doors and shutters equipped with a self-closing device,
the expansion is
EI2 30-C0, where the classes 'C0
to C5' are defined in test document prEN
13916.
|
| S - |
for elements with requirements on smoke leakage, as EI2 60-Sm when
the classification is determined under ambient conditions
Sa and/or medium temperature conditions Sm. |
| IncSlow - |
where the response to the slow heating curve has been additionally evaluated,
as EI 30-IncSlow.
|
| sn - |
where the semi-natural fire is an additional regulatory
requirement to the standard time-temperature exposure [
only relevant for lightweight horizontal protective membranes
with low thermal inertia ], and expressed as R 60-sn.
|
| ef - |
where performance against external fire exposure instead
of the standard time-temperature exposure is determined,
and expressed as EI 60-ef.
|
| r - |
where performance against constant temperature attack of
500 0C [reduced temperature exposure] instead
of the standard time-temperature exposure is determined,
expressed as RE 30-r. |
PARTICULAR PERFORMANCE PARAMETERS
G - The performance parameter G will be used for chimneys and
chimney related products designed to be resistant to soot fires,
as tested in prEN 13216-1.
K - The performance parameter K, Fire Protection Ability, will
be used for any covering which provides fire protection to products
behind it, as tested in prEN 14135 for various periods.
Presentation of Classification
The combination of R, E, I and W shall be deduced from
test data. Expanded performance parameters shall be added when
relevant.
The classification shall be presented according to the following
template, and for load-bearing elements the applied load and/or
load level shall be included in the classification report.
|
R
|
E
|
I
|
W
|
|
t
|
t
|
-
|
M
|
C
|
S
|
IncSlow
|
sn
|
ef
|
r
|
The document EN 13501-2 also lists the tests to be carried out
per application.
Other Dedicated Classifications:
Other classification terminology is used for particular applications,
as indicated in the following list:
CLASSIFICATION OF FACADES (CURTAIN WALLS) and EXTERNAL WALLS (INCLUDING
GLAZING)
Relevant tests include prEN 1364-3 and prEN 1364-4 for
parts of curtain walls.
When the elements are tested from both sides, with standard-time
temperature curve from inside, and external fire exposure
curve from outside, the lowest time determines the classification
Tests and classifications may be performed from 1 side only, inside
or outside, and in these cases, identified by -
i --> o
when classification is envisaged from inside to outside.
o --> i
when classification is envisaged from outside to inside.
o <--> i
when classification is envisaged from inside to outside and outside to inside.
i.e. compare
EI 60 (i -->o) with fire on inside only, with
EI 60 (o <--> i) for fire exposure from both outside and
inside.
CLASSIFICATION OF CEILING MEMBRANES WITH INDEPENDENT FIRE RESISTANCE
Tests are conducted to EN 1364-2 and could be for fire exposure
above the ceiling [a], or from below the ceiling [b], or
from both above and below the ceiling [ a and b].
So for a ceiling membrane providing 30 minutes integrity and insulation,
the possibilities are respectively expressed as -
EI 30 (a -->b) or EI 30 (b --> a) or EI 30 (a <-->b)
CLASSIFICATION OF PENETRATION SEALS [FOR PIPES]
When penetration seals for piped services are to be classified,
4 different pipe end configurations are defined in the test standard
prEN 1366-3, with ends capped or uncapped inside/outside the
fire test furnace.
The classification is specified for the relevant condition
as
EI 30 U/U or similar
In accordance with the table below, which defines the Pipe
End Configuration
|
Test condition
|
Pipe end configuration
|
|
Inside the furnace
|
Outside the furnace
|
|
U/U
|
Uncapped
|
Uncapped
|
|
C/U
|
Capped
|
Uncapped
|
|
U/C
|
Uncapped
|
Capped
|
|
C/C
|
Capped
|
Capped
|
CLASSIFICATION OF LINEAR JOINT SEALS
These seals ate tested in accordance with prEN 1366-4, but different
test configurations are possible, as follows
|
Test Condition
|
Designatory Letter
|
|
Specimen orientation
- horizontal supporting construction
- vertical supporting construction
- vertical joint
- vertical supporting construction
- horizontal joint
|
|
|
H
|
|
V
|
|
T
|
|
Movement capability
- No movement
- Induced movement (in %)
|
|
|
X
|
|
M%
|
|
Type of splices
- Manufactured
- Field
- Both manufactured
and field
|
|
|
M
|
|
F
|
|
B
|
|
Joint widths range (in mm)
|
W 00 to 99
|
The classification obtained for the linear joint seal is therefore
specified typically as -
EI 30 - H - M100 - B - W 30 to 90
CHARACTERISATION DATA FOR APPLIED PROTECTION TO STEELWORK
The fire tests will allow the data to be subjected to thermal analysis
so as to produce a series of tables and graphs relating to fire
resistance periods of 15, 30, 45, 60, 120, 180 and 240 minutes.
In addition, the minimum thickness of protection material will
be indicated for limiting design temperatures of 350 0C,
400 0C, 450 0C, 500 0C, 550 0C,
600 0C, 650 0C, 700 0C, 750 0C
on steel members with various section factors denoted by Am/V.
Care should be taken to ensure that any thickness data provided
is appropriate to the steel size and the appropriate limiting
design temperature selected from 350 - 750 0C.
|