PROTECTED ZONES
Where buildings are divided into 2 or more fire compartments, the
purpose of the separating compartment wall is to ensure that the
spread of fire from one compartment to another is prevented. Note
that partition walls are not compartment walls but are used to create
rooms within a fire compartment. The external enclosure of a building
will play a key role in ensuring that fire spread around or over
the compartment wall is inhibited. The specification for the fire
performance of external walls and roofs must ensure that they do
not permit the spread of fire around or over any compartment wall
within the building. The LPC Design Guide for the fire protection
of buildings introduces this concept as the 'Protected Zone' which
is defined as 'the sections of roof, external walls and supporting
frame adjacent to and within a specified distance on each side of
a compartment wall'. Designers should be aware that the external
walls, roofs and supporting frame in the protected zone may well
require a higher fire resistance than walls and roofs elsewhere in
the building, depending on the findings of the risk assessment.
 |
Extent of Protected Zone
The protected zone along the external wall is the
distance between compartment wall and the next structural member
on each side of the compartment wall. This may need to be further
extended if fire exposure from an adjacent building is likely to
compromise the compartmentation. If the next structural member is
within 1 metre of the compartment wall, the protected zone should
be extended to the next structural member. In addition, if part of
the wall is less than 1 metre from the relevant boundary, as defined
in Approved Document B - Fire Safety, supporting Building Regulations,
higher fire resistance levels will be required.
It is important that external
walls, roofs and supporting framework in the protected
zone are provided with adequate fire resistance or alternative
protection to prevent the early spread of fire from one
side to the other.
|
| -
|
For compartment walls parallel to the
line of the roof ridge, the protected zone depends on the
risk assessment for the business, but is often not less
than 5 metres.
|
| |
Note that whilst risk assessments arising
from the Fire Precautions (Workplace) Regulations 1997
are intended to protect people in buildings, the risk assessment
for the insurer will need to include both risk to people
and the business which is housed in the building, including
any business interruption which may arise.
|
| -
|
For compartment walls at right angles
to the line of the roof ridge, the protected zone should
extend to the next structural member beyond 1 metre from
the wall.
|
Fire Resistance Requirements
The requirements for protected zones will vary according to
the use of the building, the risk assessment and the associated
business risk. While actual requirements should be confirmed at
the earliest opportunity with the insurer, additional requirements
can be found in Loss Prevention Standard LPS 1181: Part 1, Appendix
B.
The figures indicated below are those appearing in the draft document
August 2002.
|
External Grade
|
Integrity
[minutes]
|
Insulation
[minutes]
|
Typical application, see Table 2.2 of LPC Design Guide
|
|
EXT -A60
|
60
|
60*
|
Retail warehouse 4b, superstore, industrial 6b, and storage
7a
|
|
EXT -A30
|
30
|
30*
|
Shop 4a, commercial, industrial 6a
|
|
EXT - A15
|
30
|
15
|
Fully sprinklered buildings
|
* Roof and external wall cladding systems which
achieve an insulation time within 90% of this figure may be deemed
to satisfy the requirements.
|
Copyright
2004 Wilhams.All rights reserved.
. |